일유체 노즐을 이용한 실내 수분무가습 방식 클린룸의 에너지소비량에 관한 실험적 연구

Full metadata record
DC Field Value Language
dc.contributor.author송원일-
dc.contributor.author박수빈-
dc.contributor.author김기철-
dc.contributor.author유경훈-
dc.contributor.author태경응-
dc.contributor.author김용식-
dc.contributor.author양지석-
dc.contributor.author송덕용-
dc.contributor.author권오명-
dc.contributor.author이건형-
dc.date.accessioned2021-09-02T19:02:18Z-
dc.date.available2021-09-02T19:02:18Z-
dc.date.created2021-06-17-
dc.date.issued2018-
dc.identifier.issn1229-6422-
dc.identifier.urihttps://scholar.korea.ac.kr/handle/2021.sw.korea/79620-
dc.description.abstractFor a recent large-scale semiconductor manufacturing plant, the air conditioning energy consumption required to maintain a cleanroom environment accounts for 40~50% of the total energy consumption in the plant. Therefore, the assessment of the air conditioning energy consumption in the cleanroom is critical for reducing energy cost in the plant. Particularly, the energy consumption required to humidify incoming outdoor air in the winter season is generally known to be high. In order to displace the huge energy consumption of steam generators like boilers in a conventional steam humidification type cleanroom, a water spray humidification technique by use of a water spray nozzles can be introduced into the air circulation path inside the cleanroom instead of the steam generators inside the outdoor air conditioning system. In the present study, a twin cleanroom experiment with each outdoor air flow of 2,300 m3/h was conducted to obtain and compare real time electric power consumption structures of a steam humidification type cleanroom and an indoor water spray humidification type cleanroom with one-fluid nozzles. In addition, a numerical calculation was carried out to assess the annual power consumptions of the two types of cleanrooms. It was concluded from the present work that the indoor water spray humidification type cleanroom was more energy-efficient and reduced the annual electric power consumption of the steam humidification type cleanroom by about 27%.-
dc.languageKorean-
dc.language.isoko-
dc.publisher대한설비공학회-
dc.title일유체 노즐을 이용한 실내 수분무가습 방식 클린룸의 에너지소비량에 관한 실험적 연구-
dc.title.alternativeAn Experimental Study on Energy Consumption in an Indoor Water Spray Humidification Type Cleanroom with One Fluid Nozzles-
dc.typeArticle-
dc.contributor.affiliatedAuthor권오명-
dc.identifier.doi10.6110/KJACR.2018.30.11.533-
dc.identifier.bibliographicCitation설비공학 논문집, v.30, no.11, pp.533 - 545-
dc.relation.isPartOf설비공학 논문집-
dc.citation.title설비공학 논문집-
dc.citation.volume30-
dc.citation.number11-
dc.citation.startPage533-
dc.citation.endPage545-
dc.type.rimsART-
dc.identifier.kciidART002401800-
dc.description.journalClass2-
dc.description.journalRegisteredClasskci-
dc.subject.keywordAuthorSemiconductor manufacturing cleanroom(반도체 클린룸)-
dc.subject.keywordAuthorIndoor water spray humidification(실내 수분무가습)-
dc.subject.keywordAuthorTwin cleanroom experiment (트윈 클린룸 실험)-
dc.subject.keywordAuthorElectric power consumption(소비전력량)-
dc.subject.keywordAuthorOne-fluid nozzle(일유체 노즐)-
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > Department of Mechanical Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher KWON, Oh Myoung photo

KWON, Oh Myoung
공과대학 (기계공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE