A Study on an Operation Strategy of Dual-Infeed HVDC System
- Authors
- Kim, Chan-Ki; Jang, Gilsoo
- Issue Date
- 1월-2017
- Publisher
- KOREAN INST ELECTR ENG
- Keywords
- HVDC; Multi-infeed HVDC; Line arrester; Voltage control
- Citation
- JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, v.12, no.1, pp.45 - 52
- Indexed
- SCIE
SCOPUS
KCI
- Journal Title
- JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY
- Volume
- 12
- Number
- 1
- Start Page
- 45
- End Page
- 52
- URI
- https://scholar.korea.ac.kr/handle/2021.sw.korea/85165
- DOI
- 10.5370/JEET.2017.12.1.045
- ISSN
- 1975-0102
- Abstract
- This paper deals with the operation strategy of reactive power in a multi-infeed HVDC (MIHVDC) system, in which several converters are connected to the same or nearby separate AC buses. The potential problems concerning a MIHVDC system when feeding a weak AC network are as follows: the need for coordination of the recovery control, the possibility of voltage instability or low quality of the area connected to the MIHVDC system, and the risk of mutual commutation failures. These problems in MIHVDC systems are similar to those in single-infeed HVDC (SIHVDC) systems, but the differences with the phenomenon of the SIHVDC system are the interactions between converters. The main reason for the potential problems of HVDC systems (MIHVDC or SIHVDC) is voltage variation; therefore, to mitigate the voltage variations, the performances of the HVDC system should be enhanced. Consequently, to mitigate the potential problems of MIHVDC systems, several solutions are suggested in this study, including installing STATCOM and installing a line arrester on the tower. The study results will be applied to a multi-infeed HVDC system in Korea.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - College of Engineering > School of Electrical Engineering > 1. Journal Articles
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.