Implementation of Under Voltage Load Shedding for Fault Induced Delayed Voltage Recovery Phenomenon Alleviation

Authors
Lee, Yun-HwanPark, Bo-HyunOh, Seung-ChanLee, Byong-JunShin, Jeong-HoonKim, Tae-Kyun
Issue Date
3월-2014
Publisher
SPRINGER SINGAPORE PTE LTD
Keywords
Fault induced delayed voltage recovery; Under voltage load shedding; Stall phenomenon; Induction motor loads; Locked rotor current
Citation
JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, v.9, no.2, pp.406 - 414
Indexed
SCIE
SCOPUS
KCI
Journal Title
JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY
Volume
9
Number
2
Start Page
406
End Page
414
URI
https://scholar.korea.ac.kr/handle/2021.sw.korea/99073
DOI
10.5370/JEET.2014.9.2.406
ISSN
1975-0102
Abstract
Significant penetration of induction Motor loads into residential neighborhood and commercial regions of local transmission systems at least partially determine a vulnerability to a fault induced delayed voltage recovery (FIDVR) event. Highly concentrated induction motor loads with constant torque could stall in response to low voltages associated with system faults. FIDVR is caused by wide spread stalling of small HVAC units (residential air conditioner) during transmission level faults. An under voltage load shedding scheme (UVLS) can be an effective component in a strategy to manage FIDVR risk and limit the any potential disturbance. Under Voltage Load Shedding take advantage of the plan to recovery the voltage of the system by shedding the load ways to alleviation FIDVR.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > School of Electrical Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher LEE, Byong Jun photo

LEE, Byong Jun
공과대학 (전기전자공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE