Performance evaluation and modeling of a hybrid cooling system combining a screw water chiller with a ground source heat pump in a building

Citations

WEB OF SCIENCE

41
Citations

SCOPUS

46

초록

The performance of a hybrid cooling system that combines a screw water chiller with a ground source heat pump (GSHP) was measured and analyzed at various cooling loads. In addition, the hybrid cooling system in a building was modelled sophisticatedly using EnergyPlus and then validated with the measured data. The coefficient of performance of the GSHP was lower than that of a conventional chiller in the monitored building, but the hybrid cooling system helped to stably provide the required cooling capacity at high-load conditions. The mean bias error and the normalized root-mean squared error of the predicted cooling load of the building were -8% and 12.4%, respectively. The hybrid cooling system was simulated by varying four operating parameters: the operating schedule, chilled water temperature (T-cw), dry-bulb temperature (T-DB), and entering water temperature (T-EW). The Tcw is ascertained as being the most effective control parameter in the hybrid cooling system. (C) 2010 Elsevier Ltd. All rights reserved.

키워드

Ground source heat pump (GSHP)Screw water chillerHVAC systemModelingAIR-CONDITIONING SYSTEMSIMULATIONVALIDATIONFLOW
제목
Performance evaluation and modeling of a hybrid cooling system combining a screw water chiller with a ground source heat pump in a building
저자
Jeon, JongugLee, SunilHong, DaehieKim, Yongchan
DOI
10.1016/j.energy.2010.01.016
발행일
2010-05
유형
Article
저널명
Energy
35
5
페이지
2006 ~ 2012