이산화탄소 급탕 열펌프의 운전조건에 따른 성능 특성에 관한 실험적 연구Experimental Study on the Performance of a CO_2 Heat Pump Water Heater under Various Operating Conditions

Other Titles
Experimental Study on the Performance of a CO_2 Heat Pump Water Heater under Various Operating Conditions
Authors
손동진백창현허재혁강훈김용찬
Issue Date
2011
Publisher
대한설비공학회
Keywords
CO_2 heat pump water heater(이산화탄소 급탕 열펌프); Water heating temperature (급탕온도); Coefficient of Performance(COP; 성능계수)
Citation
설비공학 논문집, v.23, no.4, pp.273 - 280
Indexed
KCI
Journal Title
설비공학 논문집
Volume
23
Number
4
Start Page
273
End Page
280
URI
https://scholar.korea.ac.kr/handle/2021.sw.korea/114535
ISSN
1229-6422
Abstract
In this study, the steady state performance of a CO_2 heat pump water heater was measured with a variation of operating conditions such as refrigerant charge amount, compressor frequency, EEV opening, and water mass flow rate. Transient state performance tests were also conducted to investigate major system effects associated with the interaction between the CO_2 heat pump water heater and the water tank. Optimum refrigerant charge amount for the system was 1600 g. At compressor frequencies of 50 Hz and 60 Hz, water mass flow rates of 95 kg/h and 105 kg/h, and EEV opening of 8% and 16%, the water heating temperatures were 65℃ and 68℃ and COPs were 3.0 and 2.8, respectively. In the transient condition, the instantaneous COP decreased with an increase in the inlet water temperature.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > Department of Mechanical Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher KIM, Yong Chan photo

KIM, Yong Chan
College of Engineering (Department of Mechanical Engineering)
Read more

Altmetrics

Total Views & Downloads

BROWSE