Fault analysis in the grid with inverter-based distributed generation considering the interconnection transformer topology
- Authors
- Yoon, M.; Lee, M.; Cho, N.; Choi, S.
- Issue Date
- 2021
- Publisher
- Korean Institute of Electrical Engineers
- Keywords
- Distributed generation; Fault analysis; Fault current; Interconnection transformer
- Citation
- Transactions of the Korean Institute of Electrical Engineers, v.70, no.9, pp.1274 - 1281
- Indexed
- SCOPUS
KCI
- Journal Title
- Transactions of the Korean Institute of Electrical Engineers
- Volume
- 70
- Number
- 9
- Start Page
- 1274
- End Page
- 1281
- URI
- https://scholar.korea.ac.kr/handle/2021.sw.korea/138418
- DOI
- 10.5370/KIEE.2021.70.9.1274
- ISSN
- 1975-8359
- Abstract
- For conducting the fault analysis in a system with distributed generation, the sequence equivalent circuit is used. Due to the characteristics of distributed generation that reverse currents occur, the size of the fault current can be determined by the path where fault current can flow into the fault point in the negative sequence and zero sequence. In this paper, we calculate and compare the fault currents in the system with inverter-based distributed generation considering the topology of transformer winding. From the results, we can analyze the effect of the interconnection transformer in the fault analysis. Copyright © The Korean Institute of Electrical Engineers.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - College of Engineering > School of Electrical Engineering > 1. Journal Articles
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.